Improvement of Hall Effect Current Transducer Metrological Performances in the Presence of Harmonic Distortion
2010
The performance of Hall effect current transducers (HECTs), under distorted waveform conditions, is usually characterized by means of a frequency response test. In this paper, it was investigated if frequency response is able to correctly evaluate the ratio and the phase errors under distorted conditions. Two HECTs, with the accuracy class level of 1% and 0.5%, respectively, were experimentally characterized under two conditions: 1) sinusoidal excitation with frequencies ranging from 50 to 750 Hz, which is the well-known frequency response test, and 2) nonsinusoidal excitation using fundamental frequency and one harmonic with adjusted amplitude and phase shift. It was found that ratio and p…
A novel approach to current transformer characterization in the presence of harmonic distortion
2009
The current transformer (CT) performance under distorted waveform conditions is usually characterized by means of the frequency-response test. In this paper, a new way to characterize CTs, closer to real operation conditions, is proposed. The harmonic phase-angle and ratio errors are measured using a nonsinusoidal current composed of fundamental and one harmonic with adjustable phase shift. The new method was tested by determining the performance of two metering class CTs commonly used by the Italian power company. The errors measured using the proposed approach are larger than the ones obtained with the frequency response. This result suggests that the frequency-response approach for the e…